Calculate 3 phase motor current from load power, line voltage and power factor.
This is the standard formula for calculating the line current of a balanced three-phase load — the same formula used across electrical engineering references for sizing cables, contactors, overload relays and breakers for three-phase motors, screw compressors and other industrial equipment.
Given: A 15 kW three-phase screw compressor motor runs on a 415V supply at 0.85 power factor.
Result: I = (15 × 1000) ÷ (1.732 × 415 × 0.85) = 24.6 A.
√3 (≈1.732) accounts for the 120° phase difference between the three phases when relating line current to total power in a balanced three-phase system.
Use the electrical input power in kW. If you only have HP, convert with the HP to kW calculator first, then divide by efficiency if you want input rather than output power.
Use the motor's rated full-load current (FLA) from the nameplate where available; this calculator is for estimating current when only power, voltage and PF are known.
These calculators are provided for informational and estimation purposes. Results depend on the assumptions and input values used. Always verify critical engineering calculations against applicable standards, manufacturer specifications, site measurements, and qualified professional advice.