Estimate cable voltage drop for single-phase or three-phase circuits from cable length, current and resistance.
Voltage drop along a cable run can cause motors to run hot, undervoltage trips and inefficient operation if the cable is too long or undersized. This calculator estimates the voltage drop using the cable's resistance per km (from cable catalogue tables), the load current and the one-way cable length.
Given: A three-phase circuit carries 25A over a 50m cable with resistance 1.15 Ω/km.
Result: Vd = (1.732 × 1.15 × 25 × 50) ÷ 1000 = 2.49 V.
Many electrical codes recommend keeping total voltage drop under about 3–5% of supply voltage for the full circuit run, though exact limits depend on the applicable code.
Cable manufacturers publish resistance per km for each conductor size (mm² or AWG) in their technical catalogues or datasheets.
These calculators are provided for informational and estimation purposes. Results depend on the assumptions and input values used. Always verify critical engineering calculations against applicable standards, manufacturer specifications, site measurements, and qualified professional advice.