Calculate the electricity running cost of a motor from its HP, load factor and efficiency.
Motors rarely run at exactly 100% of their rated load all the time. This calculator estimates realistic running cost by factoring in the average load a motor actually operates at, alongside its rated HP and efficiency, giving a more accurate cost figure than assuming full-load operation throughout.
Given: A 20 HP motor runs at 80% average load, 90% efficiency, 10 hrs/day, 26 days/month, at ₹8/kWh.
Result: Input kW = (20×0.7457×0.8)÷0.9 = 13.26 kW. Monthly cost = 13.26×10×26×8 = ₹27,590.
Measure current with a clamp meter and compare to the nameplate full-load current, or use an energy logger over a typical production cycle for the most accurate figure.
No — starting (inrush) current lasts only a few seconds and has negligible effect on overall energy cost compared to running load.